8510-8 supplier to order replacement parts. Both physically absent or faulty could also be the result
of the power supply not being properly seated.
FIGURE 19
Blower assembly
1. Power LED
2. Fault LED
The following table describes the LED patterns for the blower assembly.
Blower assembly LED descriptions
TABLE 9
LED purpose Color
Status
Recommended action
Power
No light (LED is off)
Blower assembly does not
have power.
Ensure that the blower assembly is
firmly seated and has power.
Steady green
Blower assembly has power.
No action required.
Fault
No light (LED is off)
Blower assembly is either
healthy or does not have
power.
Ensure that the blower assembly has
power.
Steady amber
Blower assembly has a
failure (full or partial).
Replace the blower assembly.
Slow-flashing amber (on
2 seconds, then off 2
seconds)
Blower assembly is not
seated correctly or is faulty.
Pull the unit out and reseat it. If the
LED continues to flash, replace the
unit.
Monitoring System Components
Brocade DCX 8510-8 Backbone Hardware Reference Manual
71
53-1002180-08
Содержание DCX 8510-8
Страница 1: ...53 1002180 08 19 September 2014 Brocade DCX 8510 8 Backbone Hardware Reference Manual ...
Страница 12: ...What s new in this document 12 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...
Страница 22: ...Network manageability 22 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...
Страница 34: ...Installing ICL cables 34 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...
Страница 148: ...Port Numbering Template 148 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...
Страница 166: ...Brocade DCX 8510 Technical Specifications 166 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...
Страница 172: ...Danger Notices 172 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...