exCeedInG PeRmItted PRessuRe
&/oR temPeRAtuRe LeveLs
Equipment used in combination with the BOSS™ X-POT6+ must guarantee that the
permitted operating temperature and the permitted medium temperature (heat transfer
medium) cannot be exceeded. Excess pressure and temperature may lead to component
overload, irreparable damage to components, loss of function and, as a result, to severe
personal injury and damage to property. Regular checks/inspections of these safeguards
must be carried out.
sAFeGuARds
The equipment supplied is equipped with the required safety devices. To test their
effectiveness or restore the original set-up conditions, the equipment must first be taken
out of service. Taking the system out of service implies that power should be isolated,
hydraulics isolated and then vented.
exteRnAL FoRCes
Avoid any additional forces (e.g.: forces caused by heat expansion, vibration or dead
weights on the flow and return lines).
These can lead to damage / leakage in water-bearing pipework, loss of stability of the
appliance and potentially failure of pressure bearing components.
eLeCtRICAL eQuIPment
InsPeCtIons
Regardless of the prescriptions of the property insurer / operator it is recommended to
inspect demonstrably the electrical equipment of the BOSS™ X-POT6+ together with the
heating or chilled installation at least every 12 months.
mAIntenAnCe & RePAIR
These services may only be carried out when the X-POT6+ is shut down. The BOSS™
X-POT6+ equipment must be taken out of service and guarded against unintentional re-
starting until the maintenance work is finished.
The control panel can be interconnected to a BMS or alarm system to allow for indication
that the filter is ready for change and the magnets are ready for cleaning.
The VEXO
®
iX-1 Controller is fitted with a combined visual illuminated flashing beacon in
low light situations for visual indication and sounder as an indication of filter blockage.
The unit must be inspected on an annual basis, and the electrical and mechanical
components verified for operation and integrity.
(See inspection table on page 9)