dosInG (ContInued)
3. Manually Dosing the System with Treatment Chemicals
WARNING
This equipment must only be used, maintained or serviced by trained competent
engineers. If in any doubt please do not touch this equipment.
For further advice please contact BSS Industrial or your reseller for additional
information and guidance.
WARNING
This equipment uses Rare Earth Magnets with a strong magnetic field.
You should not use, service or work in the close vicinity (30cm / 1ft of this
equipment if you are fitted with a pacemaker or other electromechanical
medical devices.
1.
The operative must wear protective gloves and eyewear for this operation.
2.
Use of the main BOSS™ X-POT6+ Schematic (page 10) is required to follow the main
Item Numbers.
3.
Turn the power off to the BOSS™ X-POT6+ unit by turning the Mains ON/OFF Power
Switch (22) through 90
o
.
4.
Check to see the power is off, the power to the VEXO
®
iX-1 Controller (21). The screen
should be blank and off and the pump will not run.
5.
Manually close the 1” Isolating Valves (1&3) on the Dirty Flow to the BOSS™ X-POT6+.
6.
Manually close the 1” Isolating Valves (8 & 11) on the Clean Return from the BOSS™
X-POT6+.
7.
Manually open the 1” Isolating Valve (12). This will open the BOSS™ X-POT6+ Vessel
(4) to drain.
8.
Remove the
½
” plug and manually open the
½
” Manual Vent Isolating Valve (19). This
will open the BOSS™ X-POT6+ Vessel (4) to atmosphere and will help the BOSS™
X-POT6+ Vessel (4) drain quicker.
NOTE: If the system water is hot, leave enough time for the water to cool sufficiently
before working on this vessel.
9.
Un-tie and remove the top insulation cover and store in a clean and dry place.
10.
Once you are content that all of the liquid within the vessel has been drained out;
11.
Carefully loosen the 8off nuts which hold the lid in place. Please ensure the nuts
are loosen in an opposite order, for example, front then back, then left to right and
diagonals etc.
12.
Once all of the nuts have been loosened sufficiently, undo the nut to the end of the
bolt and swing the arms of the bolts down to the side of the Vessel.
13.
The lid of the vessel can now be carefully removed and placed on a clean dry surface.
14.
Remove the 6 Magnet Grate (5) by the handle and place the Magnet Grate (5) onto a
flat surface.
Continued on next page