X-POT6+ Operation & Maintenance Manual
(V1.2 September 2017)
Page 22
dosInG & WAteR tReAtment
ChemICALs
To manually dose the system, it may only be carried when the system is shut down and
the BOSS™ X-POT6+ has been hydraulically isolated from the main system water pressure
and also electrically isolated from the main system power supply.
The X-POT6+ equipment must be taken out of service and guarded against un-intentional
re-starting until the Water Treatment Chemicals are dosed into the X-POT6+ Vessel (4).
Dosing of Water Treatment Chemicals can only be achieved when the main System Pumps
are operational, make sure they are working and the system is running.
BSS Industrial recommend the ‘X-PO’ Range of Water Treatment
Chemicals for use in Commercial Heating and Cooling Systems.
BOSS™ X-PO10
BOSS™ X-PO20
BOSS™ X-PO35
BOSS™ X-PO40
BOSS™ X-PO45
Commercial
Inhibitor
De-Scaling
Agent
Sanitiser and
Cleanser
(Non-Flush)
Heavy Duty
De-Sludger
New System
Cleaner
BOSS™ X-PO50
BOSS™ X-PO55
BOSS™ X-PO60
BOSS™ X-PO65
BOSS™ X-PO80
Monopropylene
Non Hazardous
Glycol
Anti-Freeze,
Ready Mixed
Monopropylene
Non Hazardous
Glycol
Anti-Freeze,
Concentrate
Monoethylene
Glycol
Anti-Freeze,
Ready Mixed
Monoethylene
Glycol
Anti-Freeze,
Concentrate
System
Biocide
Note:
The safety circuits and data transmissions (if applicable) made or broken while shutting
down and could trigger the BMS Alarms or lead to false failure information.
•
Operating instructions for relevant system heating or cooling units must be observed.
To make the hydraulic components safe, isolate the relevant sections and vents using
the relevant drain valves and relieve the pressure.
•
The equipment is to be worked on only when in a safe and cool condition.
•
Do not attempt to work on this equipment at elevated temperatures.
•
Use of eye/face/hand protectors is required as the eyes or face could be injured by
spraying fluids if the isolating valves have not been closed properly.