ix-1 ContRoLLeR monItoRInG
Volt free contacts are provided for the following conditions. The contacts are rated 5
amp, 230v maximum
Filter On
– In Normal Operation, the VEXO
®
iX-1 Controller will
scroll “
Filter Pump Run
”.
The screen scrolls:
:
<
Filter Pump Run
>
In the event the filter is blocked, the VEXO
®
iX-1 Controller will
scroll “
Blocked Filter
”
– Filter Blocked, Clean / Replace Filters
The screen scrolls:
:
<
Blocked Filter
>
In the event of a Dirty Flow Pressure Transducer failure, the
VEXO
®
iX-1 Controller will scroll “
Sensor 1 Fail
”
- Pressure Transducer Dirty Flow Failure
The screen scrolls:
:
:
<
Sensor 1 Fail
>
In the event of a Clean Return Pressure Transducer failure, the
VEXO
®
iX-1 Controller will scroll “
Sensor 2 Fail
”
- Pressure Transducer Clean Return Failure
The screen scrolls:
:
<
Sensor 2 Fail
>
In the event the X-POT6+ Circulating Pump fails to operate,
the VEXO
®
iX-1 Controller will scroll “
Pump Fail
”
– Flow Pump Failure
The screen scrolls:
:
:
<
Pump Fail
>
1. vexo
®
ix-1 ContRoLLeR PARAmeteRs
No
Parameter
Default Value
Range
0
Pressure Differential
0.4 Bar
0.0 – 1.0 Bar
1
Alarm Relay Contacts
0
0 = N/C 1 = N/C
2
Sensor Minimum Pressure
0 Bar
0.0 – 10.0 Bar
3
Sensor Maximum Pressure
10 Bar
0.0 – 10.0 Bar
4
ID Number
0
5
Pump Hours
6
Alarm Count