Service reminder | 57
F .2
Lockout codes
Error no .
Error
Description
0
E2PROM_READ_ERROR
Internal software error
1
IGNIT_ERROR
Three unsuccessful ignition attempts in a row
2
GV_RELAY_ERROR
Failure detected in the GV relay
3
SAFETY_RELAY_ERROR
Failure detected in safety relay
4
BLOCKING_TOO_LONG
Control had a blocking error for more than 20 hours
5
FAN_ERROR_NOT_RUNNING
Fan is not running for more than 60 seconds
6
FAN_ERROR_TOO_SLOW
Fan runs too slow for more than 60 seconds
7
FAN_ERROR_TOO_FAST
Fan runs too fast for more than 60 seconds
8
RAM_ERROR
Internal software error
9
WRONG_EEPROM_SIGNATURE
Contents of E2prom is not up to date
10
E2PROM_ERROR
Wrong safety parameters in E2prom
11
STATE_ERROR
Internal software error
12
ROM_ERROR
Internal software error
13
APS_NOT_OPEN
Air pressure switch not working
14
APS_NOT_CLOSED
Air pressure switch not working
15
MAX_TEMP_ERROR
The external overheat protection is enabled or the
T_Supply
sensor
measures a temperature of over 100°C (212°F)
16
FLUE_GAS_ERROR
Flue temperature exceeded the maximum flue temperature
17
STACK_ERROR
Internal software error
18
INSTRUCTION_ERROR
Internal software error
19
ION_CHECK_FAILED
Internal software error
20
FLAME_OUT_TOO_LATE
Flame still present 10 seconds after closing the gas valve
21
FLAME_BEFORE_IGNIT
Flame is detected before ignition
22
TOO_MANY_FLAME_LOSS
Three time flame lost during 1 demand
23
CORRUPTED_ERROR_NR
Error code RAM byte was corrupted to an unknown error code.
24
FLUE_SWITCH_NOT_CLOSING
The blocked flue sensor is not closed within 10 minutes
25
TSUPPLY_DIFF_ERROR
The 2 supply sensors deviate too much for more than 60 seconds
26
TFLUE_DIFF_ERROR
The 2 flue sensors deviate too much for more than 60 seconds
27
FILLING_TOO_MUCH
Too many automated filling attempts in a short time period
28
FILL_TIME_ERROR
Filling takes too long
29
PSM_ERROR
Internal software error
30
REGISTER_ERROR
Internal software error
31
T_EXCHANGE_LOCK_ERROR
Exchange temperature exceeded the maximum temperature.
32
T_EXCHANGE_DIFF_ERROR
The 2 exchange sensors deviate too much for more than 60 seconds
33
LWCO_1_ERROR
Low water cut-off 1 error
34
LWCO_2_ERROR
Low water cut-off 2 error
35
GAS_PRESSURE_ERROR
Gas pressure switch is open
36
AIR_DAMPER_LOCKING
Air Damper feedback is not received when the relative output is closed for the
fourth time.
37
FLUE_PRESSURE_LOCKING
Flue pressure switch is closed for the fourth time.
F .3
Blocking codes
Error no .
Error
Description
100
WD_ERROR_RAM
Internal software error
101
WD_ERROR_ROM
Internal software error
102
WD_ERROR_STACK
Internal software error
103
WD_ERROR_REGISTER
Internal software error
104
HIGH_LIMIT_FAIL
Physical high limit test failed
105
HIGH_TEMP_ERROR
Supply temperature exceeds 110°C with gas valve closed