62 | Service reminder
Appendix H - Cascade parameter
Specific Parameters
Level
(Default) Value
Range
°C
°F
°C
°F
Emergency_Mode
[-]
1: User
Enable
Enable/
Disabled
Cascade_Setpoint
Cascade CH Setpoint
[°C/°F]
1: User
60
140
40..93
104..200
Boiler_Address
[-]
2: Installer
0
0...16
0...16
Emergency_Setpoint
[°C/°F]
2: Installer
70
158
20..90
68..194
Delay_Period_Start_Next_Dependent
Start Delay Time
[sec]
2: Installer
180
0..1275
Delay_Period_Stop_Next_Dependent
Stop Delay Time
[sec]
2: Installer
180
0..1275
Delay_Period_Start_Next_Dependent_ Faster
Quick Start Interval
[sec]
2: Installer
30
0..1275
Delay_Period_Stop_Next_Dependent_ Faster
Quick Stop Interval
[sec]
2: Installer
30
0..1275
Hyst_Down_Start_Burner
Start Burner Diff
[°C/°F]
2: Installer
5
9
0..20
0..36
Hyst_Up_Stop_Burner
Stop Burner Diff
[°C/°F]
2: Installer
2
4
0..20
0..36
Hyst_Up_Stop_All
Stop Burner Diff
[°C/°F]
2: Installer
6
11
0..30
0..54
Hyst_Down_Quick_Start
Start Burner Diff in short time
[°C/°F]
2: Installer
10
18
0..20
0..36
Hyst_Up_Quick_Stop
Stop Burner Diff in short time
[°C/°F]
2: Installer
4
7
0..20
0..36
Max_Range_Up_Limit
Calculated setpoint Max offset down
[°C/°F]
2: Installer
20
36
0..20
0..36
Max_Range_Down_Limit
Calculated setpoint Max offset up
[°C/°F]
2: Installer
20
36
0..20
0..36
Start_Modulation_Delay_Factor
[-]
2: Installer
60
0..60
0 = Disabled
Next_Burner_Start_Rate
[%]
2: Installer
80
10..100
Next_Burner_Stop_Rate
[%]
2: Installer
25
10..100
Burnerr_Rotation_Interval
[days]
2: Installer
5
0..30
0 = Disabled
Calc_Setp_PID_P
[-]
3: Factory
50
0..1275
Calc_Setp_PID_I
[-]
3: Factory
50
0..1275
PID_Slew_Rate_Step_UP
[°C/100ms]
3: Factory
1,0
0..25,5
0 = Disabled
PID_Slew_Rate_Step_Down
[°C/100ms]
3: Factory
1,0
0..255
0 = Disabled
System_Pump_Post_Pump_Time
[sec]
2: Installer
30 sec
1..90