40 | Main control
Parameters
Behaviour
Graphical view
Min_EX_Flow_Rate
has
a value.
Nominal_EX_Flow_Rate
is 0.
In this case only the
Min_EX_Flow_Rate
parameter is taken in account.
The Burner switches OFF if the flow is lower than the
Min_EX_Flow_Rate
parameter and generates a
warning.
Otherwise the maximum power of the burner is fully
available
Max. available power (%)
Min. Flow
Max.(100%)
Min
Flow (m
3
/h)
0%
Min_EX_Flow_Rate
has a
value.
Nominal_EX_Flow_
Rate
has a value.
The Burner switches OFF when the flow is below
Min_EX_Flow_Rate
parameter and generates a
warning.
If the flow is in the range of
Min_EX_Flow_Rate
and
Nominal_EX_Flow_Rate
parameter the
maximal power of the burner is linear limited
If the flow is above the
Nominal_EX_Flow_Rate
parameter the maximum power of the burner is fully
available
Max. available power (%)
Min. Flow Nominal Flow
Max.(100%)
Min
Flow (m
3
/h)
0%
Relevant variables
Specific Parameters
Level
(Default)Value
Range
Min_EX_Flow_Rate
Minimal Flow threshold
2: Installer
50 l/min (13 gpm)
0...100 l/min (0...26 gpm)
Nominal_EX_Flow_Rate
Nominal Flow threshold. If 0 only the Min_EX_Flow_Rate is
taken in account for the low flow protection
2: Installer
0
0...100