SSB
6720892984 (2019/02) US
M .4 .2 Burner/Module 2 Status and Control Registers
HR #
Access
Description
Range
R
W
Module/Burner 2-8 status info
40100
-
40152
X
Burner/Module 2
(see also holding register contents “M.4.1 Burner/Module 1 Status and Control Registers” pag. 80)
M .5
Data Type
Modbus communicates using words (the contents of 16bit holding registers).
This means data will be received/send as 16-bit data for each holding register.
Some data types require a higher precision than a whole number (integer), these data types will be multiplied with a factor so the precision is not lost.
When the value for that data type is read it must be divided by the same factor to get the real value.
This also applies to writing the value, then the value must first be multiplied by the factor before writing it to the Holding register.
Data type
Resolution
Factor
Unit
Temperature
xxx.x
10
Degrees Celsius °C
Voltage
xxx.x
10
Volt
Pressure
xxx.x
10
Bar
Flame current (micro amps)
xxx.x
10
μA
Percentage
xxx.x
10
%