CH Setpoint calculated with an extra correction
The calculated setpoint based on the outdoor temperature can also be adjusted with another correction. The generation of this
extra correction is a result of a not linear computation.
The new setpoint is calculated as follow:
New CH calculated setpoint (@Outdoor_temp)= CH calculated setpoint (@Outdoor_temp) – extra correction (@Outdoor_temp)
The parameter used for the extra compensation is E2_CH_Reset_Curve_Comp .
20
CH
SE
TP
OI
NT
(°
C
/
)
°F
OUTDOOR TEMP. (°C/ )
°F
Reset Curve
Design Boiler
93
Reset Curve Outdoor Design
1)Reset Curve Outdoor Mild Weather
2) Warm Weather Shutdown
Reset Cuve
Boiler Mild
Weather
Reset Curve Boiler Maximum
200
82 180
71 160
60 140
120
49
100
38
27
80
60
16
°C °F
-6
40
4
60
16
80
27
100
38
°F
°C
Reset Curve Boiler Minimum
CH outdoor reset curve in red color and CH outdoor reset Curve with extra compensation in blue
Relevant variables
Specific Parameters
Level
(Default) Value
Settable
°C
°F
°C
°F
CH_Mode
2: Installer
0
0, 1, 2, 3, 4
CH_Hysterese_Up
[°C/°F] 3. Factory
5
9
0..20
0..36
CH_Hysterese_Down
[°C/°F] 3. Factory
5
9
0..20
0..36
Reset_Curve_Boiler_Minimum
Sets the lower limit for the CH setpoint (minimum).
[°C/°F] 2: Installer
30
86
4..82
39..180
Reset_Curve_Boiler_Maximum
Sets the upper limit for the CH setpoint (maximum).
[°C/°F] 2: Installer
80
176
27..90
81..194
Reset_Curve_Design_Boiler
Sets high boiler CH setpoint when outdoor temp. is equal to Reset_Curve_
Outdoor_Design. The range for this parameter is limited by the Reset_
Curve_Boiler_Minimum and Reset_Curve_Boiler_Maximum parameters!
[°C/°F] 2: Installer
80
176
Reset_Curve_Outdoor_Design
Sets the outdoor temp at which the boiler setpoint must be high as set by
Reset_Curve_Design_Boiler.
[°C/°F] 2: Installer
-5
23
-20..25
-13..77
Reset_Curve_Boiler_Mild_Weather
Sets low boiler CH setpoint when outdoor temp. is equal to Reset_Curve_
Outdoor_Mild_Weather. The range for this parameter is limited by the Reset_
Curve_Boiler_Minimum and Reset_Curve_Boiler_Maximum parameters!
[°C/°F] 2: Installer
40
104
Reset_Curve_Outdoor_Mild_Weather
Sets the outdoor temp at which the boiler setpoint must be low as set by
Reset_Curve_Mild_Weather.
[°C/°F] 2: Installer
20
68
0..30
32..86