6720892984 (2019/02) US
SSB
56 | Service reminder
Error History
The last 15 lockout and 15 blocking errors are stored in the boiler control. This boiler history can be shown via the Boiler History screen in LabVision or via
the installer boiler status menu in one of the advanced epHS displays.
Time Stamp
A time stamp will be added to an error at the moment the error occurs. The time between this error and a new error will be counted. The interval between
an error and the previous error is shown as interval time in minutes, hours, days or weeks.
The previous error codes are also shown in LabVision (also see the image on the following page).
Successful ignitions
To prevent wear on the e2prom of the boiler control, the successful ignitions are only saved after 16 successful ignitions. When a power cycle is performed
after 15 successful ignitions, these 15 ignitions are not counted.