76 | Service reminder
M .1
Modbus
M .1 .1
Configuration
The table below summarizes the Slave Modbus configuration details for 900TS.
Protocol
Modbus RTU.
Default dependent address
Boiler 1 Default: 1
Boiler 2 Default: 2
Boiler 3 Default: 3
Boiler 4 Default: 4
Supported Modbus commands
Read Holding registers (03)
Write single holding register (06)
Write multiple holding registers (10)
Baud rate
9600 bps.
Data Length
8
Parity
None
Stop Bits
Default: 2 stop bits
Physical layer
RS485 (two wire + optional GND)
M .2
Registers
The Cascade Manager controls the cascade of multiple boilers. Each boiler can have up to 8 units/burners available.
M .2 .1 Touch screen
Touch screen information and settings.
CLIMATIC CURVE
HR #
Access
Description
Range
R
W
Climatic curve status info
20021
X
Outdoor sensor temperature
-50...150°C (-58...302°F)
Climatic curve settings
21000
X
X
Reset Curve Boiler Design
0-100°C (32-212°F)
21001
X
X
Reset Curve Boiler Mild Weather
0-100°C (32-212°F)
21002
X
X
Reset Curve Outdoor Mild Weather
0-100°C (32-212°F)
21003
X
X
Reset Curve Outdoor Design
0-100°C (32-212°F)
21004
X
X
Warm Weather Shutdown
0-100°C (32-212°F)
21005
X
X
Reset Curve Boiler Maximum
0-100°C (32-212°F)
21006
X
X
Reset Curve Boiler Minimum
0-100°C (32-212°F)
21007
X
X
Night Setback
0-100°C (32-212°F)
Содержание SSB1000 SA