78 | Service reminder
M .3
Module/Burner Cascade Manager
Module/Burner cascade information and settings.
M .3 .1 Boiler address
HR #
Access
Control Settings
Range
R
W
Climatic curve status info
31000
X
X
Boiler address (1=Cascade / Boiler manager, 2-4=Dependent)
1 - 4
M .3 .2 Module/Burner Cascade Status
HR #
Access
Description
Range
R
W
System status info
30000
X
Power level for the boiler
0-100%
30001
X
Boiler supply setpoint (calculated)
0-100%
30002
X
Heat demand type
None,CH,DHW
30020
X
Boiler Supply temperature
0-100%
30021
X
DHW temperature
0-100%
30060
X
CH pump running
0=Off, 1=On
30061
X
DHW pump status
0=Off, 1=On
30080
X
Burn hours (total of all unit/burner burn hours)
0-65536hr
Module/Burner available
30100
X
Module/Burner 1 available / present
0=No, 1=Yes
30101
X
Module/Burner 2 available / present
0=No, 1=Yes
Module/Burner active (heating) (see also holding register contents “M .4 .1 Burner/Module 1 Status and Control Registers” pag . 80)
40000
X
Module/Burner 1 is active / heating
State(*)
40100
X
Module/Burner 2 is active / heating
State(*)
Module/Burner errors (see also holding register contents “M .4 .1 Burner/Module 1 Status and Control Registers” pag . 80)
40001
X
Module/Burner 1 has error
255=No error, x=Error
40101
X
Module/Burner 2 has error
255=No error, x=Error
The State(*) can be divided in the following steps:
Standby: 0 : Initialization
1 : Reset
2 : Standby
Active: 3/4 : Pre Purge
5/6 : (Pre) Ignition 7 : Flame Proving 8/9 : Burn 10/11 : Post Purge
Error:
12 : Error
13 : Alarm
14 : Warning
15 : Burner Boot