Service reminder | 77
M .2 .2 Boiler Cascade Manager
Boiler cascade information and settings.
BOILER CASCADE STATUS (ONLY AVAILABLE ON THE CASCADE MANAGER)
HR #
Access
Description
Range
R
W
System status info
20000
X
Power level for entire (boiler) cascade system
0-100%
502
X
X
Cascade Ch Mode X setpoint
0-100%
20001
X
System supply setpoint
0-100%
20020
X
System supply sensor temperature
-50...150°C (-58...302°F)
20021
X
Outdoor sensor temperature
-50...150°C (-58...302°F)
20060
X
Cascade Pump Status
0=Off, 1=On
Boilers available
20100
X
Boiler 1 available / present
0=No, 1=Yes
20101
X
Boiler 2 available / present
0=No, 1=Yes
20102
X
Boiler 3 available / present
0=No, 1=Yes
20103
X
Boiler 4 available / present
0=No, 1=Yes
Boilers active (heating)
20132
X
Boiler 1 is active / heating
0=No, 1=Yes
20133
X
Boiler 2 is active / heating
0=No, 1=Yes
20134
X
Boiler 3 is active / heating
0=No, 1=Yes
20135
X
Boiler 4 is active / heating
0=No, 1=Yes
Boiler errors
20164
X
Boiler 1 has error (one or more modules / burners have an error)
0=No, 1=Yes
20165
X
Boiler 2 has error (one or more modules / burners have an error)
0=No, 1=Yes
20166
X
Boiler 3 has error (one or more modules / burners have an error)
0=No, 1=Yes
20167
X
Boiler 4 has error (one or more modules / burners have an error)
0=No, 1=Yes
Boiler service
20196
X
Boiler 1 requires service
0=No, 1=Yes
20197
X
Boiler 2 requires service
0=No, 1=Yes
20198
X
Boiler 3 requires service
0=No, 1=Yes
20199
X
Boiler 4 requires service
0=No, 1=Yes