6720892984 (2019/02) US
SSB
68 | Service reminder
K .3 .2 Status Information (100 - 199)
Holding
register
Access
Description
Automatic
Conversion
Range
R
W
Status information
100
0064
X
State
See state table
101
0065
X
Status
See status table
102
0066
X
Error Code
See error list
...
Reserved...
109
Reserved
110
X
CH pump
Yes
0/100 or 0..100%
111
X
DHW pump
Yes
0/100 or 0..100%
112
X
General pump
Yes
0/100 or 0..100%
...
Reserved…
119
Reserved…
Sensor / Feedback information
120
X
Supply temperature
Yes
Depending on units °C/°F
121
X
Return temperature
Yes
Depending on units °C/°F
122
X
DHW temperature
Yes
Depending on units °C/°F
123
X
Flue gas temperature
Yes
Depending on units °C/°F
124
X
System (Heat exchanger) temperature (if available)
Yes
Depending on units °C/°F
125
X
Outside temperature (if available)
Yes
Depending on units °C/°F
...
Reserved…
139
Reserved…
140
X
Firing Rate (power output)
Yes
0..100%
142
X
Flame (ionization) current
Yes
0..x μA
143
X
Water pressure (if available)
Yes
Depending on units bar/psi
...
Reserved…
159
Reserved…
K .3 .3 Dependent Information (300 - 399)
Holding
register
Access
Description
Automatic
Conversion
Range
R
W
Dependent 01
300
X
State
See state table
302
X
Error Code
See error list
303
X
Firing Rate (power output)
Yes
0...100%
...
Reserved…
305
Reserved…
Dependent 02
306
X
State
See state table
308
X
Error Code
See error list
309
X
Firing Rate (power output)
Yes
0...100%
...
Reserved…
311
Reserved…
Dependent 03
312
X
State
See state table
314
X
Error Code
See error list
315
X
Firing Rate (power output)
Yes
0...100%
...
Reserved…