Element
Usage/Description
[Ambient]
Clicking this button causes the system to interrogate the current
ambient levels of all SE receivers on this SE coordinator.
[Revision]
Clicking this button causes the system to interrogate the RF micro
revision levels of all SE receivers on this SE coordinator.
[Jamming]
An SE receiver monitors the ambient level during normal operation.
If the ambient level rises above the jamming setting and jamming
trouble, it is reported to the Central Console. The SE receiver’s
jamming level can be adjusted by selecting the appropriate setting
(shown in hexadecimal levels) and clicking the
[Jamming]
button.
[Jam map]
Clicking this button causes the system to interrogate the jamming
setting levels of all SE receivers on this SE coordinator.
[Cancel]
Clicking this button closes the dialog window.
Put this receiver in setup mode
This button initiates the setup process by causing both the red and green LED of the selected
SE receiver to light up. The red and green LED will be flashing. On the Central Console, this
button changes to the
[Abort setup for this MUX point]
button to be able to proceed to the
next device in the event that one receiver is not set up properly.
Figure
10.25: Abort button to remove a device from the Setup Mode
The next step is to use a maintenance transmitter to transmit an alarm while standing near the
SE receiver.