Name
Color
State
Description
MS
CSos module status
Off
Red/green flash‐
ing
GN
RD
Self test or configuration is active or required.
Green flashing
GN
Module is in "Stop" state. The outputs are "0".
Green on
GN GN
The outputs are valid.
Flashing red
RD
Recoverable error. Recoverable errors are for example configuration errors of
the Csos firmware.
Red on
RD RD
Unrecoverable error. It is possible that the module has to be replaced.
NE
CSos safety network status
Off
Module has no connection to the originator
Green flashing
GN
The connection to the originator is established, but no I/O data is exchanged.
Green on
GN GN
I/O data is exchanged with the originator.
Flashing red
RD
I/O connection to originator failed.
Red on
RD RD
An error was detected in the connection that does not allow further process‐
ing.
Red/green flash‐
ing
GN
RD
The module is ready to set a new TUNID via DIP switches. The new TUNID is
applied upon the next voltage startup.
00-07
Status per output 0-7
Off
Output, logic "0".
Green on
GN GN
Output, logic "1".
DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
Bosch Rexroth AG
17/85
IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
Product description