RE 92076-01-B/2021-04-22, Bosch Rexroth AG
Commissioning |
A4... with HS5E(V)(L) control system Series 1x and 30 81
/104
The individual calibration functions can be started via IndraWorks and the "Pump
controller calibration" dialog.
Fig. 32: Calibration
For calibrating the HS5E(V)(L) control system, the hydraulic fluid must have reached
operating temperature.
Attention: the calibration function of the swivel angle zero point does not ensure
that the pressure in
A
and
B
is reached in the closed circuit at 0% swivel angle
specification.
If this is desired, the swivel angle zero point has to be readjusted manually.