en | Replacing a Power-Fan Canister in the Controller-Drive Tray
E2600 DSA E-Series iSCSI Disk Arrays
- | V2 | 2012.09
Installation Manual
Bosch Security Systems
Figure 15.4
LEDs on a DC Power-Fan Canister
7.
Turn off the Power switch on the DC power-fan canister that has failed.
Figure 15.5
Power Connector
1
Standby Power LED (Green)
2
Power-Fan Output DC Power LED (Green)
3
Power-Fan Service Action Allowed LED (Blue)
4
Power-Fan Service Action Required LED (Amber)
5
Power-Fan Input DC Power LED (Green)
WARNING!
Risk of electrical shock
Before removing or installing a power supply, turn off the power switch, and unplug the power
cord.
WARNING!
Risk of electrical shock
This unit has more than one power source. To remove all power from the unit, all DC MAINS
must be disconnected by removing all power connectors (item 4 below) from the power
supplies.
1
Supply (Negative), Brown Wire, –48 VDC
2
Return (Positive), Blue Wire
3
Ground, Green and Yellow Wire
4
DC Power Connector
CAUTION!
Electrical grounding hazard
This equipment is designed to permit the connection of the DC supply circuit to the earthing
conductor at the equipment.