vapor pressure
17.18.4 Default pressure 1 … 3
Default value for the pressure. If the "Absolute pressure mode" is set to "Default", all calculations are
carried out with this default value. If a pressure transmitter is connected, this value is only used for
calculation if a measuring fault has occurred.
Range:
-1 bar ... 300 bar
17.18.5 End pressure 1 … 3
Pressure at which the pressure transmitter supplies 20 mA.
Range:
-1 ... 300 bar
17.18.6 Start pressure 1 … 3
Pressure at which the pressure transmitter supplies 0/4 mA.
Range:
-1 ... 300 bar
17.18.7 Offset pressure 1 … 3
Offset value of the pressure measurement. This way it is possible to compensate for hydrostatic
pressure caused by the installation.
Range:
0.00 bar ... 2.00 bar
Example:
In case of a separate installation and a height difference of 4.5 m between the tube center (with
steam: condensate level) and the transmitter center, a value of 0.45 bar has to be set.
17.18.8 Pressure input
Electrical assignment of the current input to the measured value.
Range:
I1, I2, I3, I4
17.19
Temperature
17.19.1 Temperature mode 1 … 3
Operating mode for the temperature sensor (PTxxxx).
Selection: Default
Calculation with default value
PT100..1000
Measurement PT100, PT500, PT1000
0/4..20mA
Measurement via current input 1 ... 4
boiling temperature
calculated from pressure
17.19.2 Default temperature 1 … 3
Default value for the temperature. If the "Temperature mode" is set to "Default", all calculations are
carried out with this default value. If a temperature sensor is connected, this value is only used for
calculation if a measuring fault has occurred.
Range:
-100°C ... 1500 °C
17.19.3 Temperature input
Electrical assignment of the input to the measured value.
Range:
PT1, PT2, I1, I2, I3, I4
17.19.4 End temperature 1 ... 3
Scaling of the temperature input in current input mode.
Temperature at which the transmitter supplies 20 mA.
Range:
-100°C ... 1500°C.
17.19.5 Start temperature 1 ... 3
Scaling of the temperature input in current input mode.
Temperature at which the transmitter supplies 0/4 mA.