Universal Flow Computer UR06
Operating Manual
Page 48 of 55
Subject to changes
A-EN-08728-URRev.B
Bopp & Reuther
Messtechnik GmbH
Pressure 3 [bar]
Current input 2
Power 3 [kW]
Temperature 1 [°C]
Current input 3
Vapor pressure 1
Temperature 2 [°C]
Current input 4
Vapor pressure 2
Temperature 3 [°C]
17.22.2 Default current output 1 ... 2(6)
Default value for checking the current transmission and for test purposes.
Range:
0 ... 22 mA
17.22.3 End current output 1 ... 2(6)
Scaling of the current output.
Range:
-50 ... 100000.
17.22.4 Start value current output 1 ... 2(6)
Scaling of the current output.
Range:
-50 ... 100000.
17.22.5 Time constant current output 1 ... 2(6)
Damping factor for the current output. Tau ~ n * 125 ms.
Range:
n = 1 ... 255
17.22.6 Error behavior current output 1 ... 2(6)
Behavior of the current output if an error occurs. Depending on the setting, the current output retains
its value or changes to the set constant current. This can be used for remote transmission of the error
message, if supported by the evaluation device.
Selection:
Without
Default
0 mA
(equivalent to min. or line break)
3.5 mA
4 mA
(equivalent to min.)
20 mA
(equivalent to max.)
22 mA
17.22.7 Level current output 1 ... 2(6)
Selection of the current output level.
Selection: 0 ... 20 mA,
4 ... 20 mA
17.23
Clock
17.23.1 Date
Display and setting of the date.
Range:
01.01.00 ... 31.12.99
17.23.2 Time
Display and setting of the time.
Range:
00:00:00 ... 23:59:59
17.23.3 Clock adjustment
Adjustment of the real time clock.
Range:
0.999005 ... 1.00019