P aram eter s
4
User instructions. DGM speed regulator
127
5.3.13 Block detection
5,080
Block detection
Unit: whole
Relation with
the parameter:
5,081
34,110
Parameter
manual:
P. xy
Acquisition status:
2
min.:
0
value (enter!)
max.:
1
Def.:
0
Block detection can be activated with this parameter.
0 = inactive
1 = active
This function works reliably only if the motor data has been entered correctly
and the slip compensation has not been deactivated.
5,081
Blocking time
Unit: s
Relation with
the parameter:
5,080
Parameter
manual:
P. xy
Acquisition status:
2
min.:
0
value (enter!)
max.:
50
Def.:
2
Indicates the time after which a block is detected.
5,082
Start error active
Unit: whole
Relation with
the parameter:
4,233
Parameter
manual:
P. xy
Acquisition status:
2
min.:
0
value (enter!)
max.:
1
Def.:
1
The start error is defined as follows: 10% of the nominal motor frequency
reached after 30 seconds (if nominal frequency is < 10%, the error is not
generated). If the acceleration time is > 30 seconds, instead of 30 seconds,
half of the acceleration ramp time is considered.
0 = function deactivated
1 = function active