Troubl e shooti ng
User instructions. DGM speed regulator
145
No.
Error name
Error description
Possible causes/remedies
10
Parameter distributor
The internal distribution of the
parameters during initialization
failed
Parameter set incomplete
11
Power time-out
The part related to power
does not react
Operation with 24 V without
network power supply
13
Breakage of the analog
In1 cable (4..20 mA / 2
– 10 V)
Current or voltage below the
lower limit of analog input 1
(the checking of this error is
activated by setting the
parameter 4.021 to 20%).
Cable breakage, external
sensor defective
14
Breakage of the analog
In 2 cable (4..20 mA / 2
– 10 V)
Current or voltage below the
lower limit of analog input 2
(this error monitoring is
activated by setting the
parameter 4.051 to 20%)
Cable breakage, external
sensor defective
15
Block detection
The motor transmission shaft
is blocked. 5,080
Eliminate the block
16
PID dry cycle
No actual PID value even
though number of revs is at
the maximum
Actual PID value sensor
defective. Extension of the
dry cycle time parameter
3.072
17
Start error
The motor does not function
or does not function correctly.
5,082
Check the motor
connections/motor and
regulator parameters;
deactivate the error if
necessary (5.082).
18
CF application
overheating
Excessive internal
temperature
Cooling insufficient, low
number of revs and high
torque, excessive pulse
frequency.