P aram eter s
4
User instructions. DGM speed regulator
102
1,180
Reset function
Unit: whole
Relation with
the parameter:
1,181
1,182
Parameter
manual:
P. xy
Acquisition status:
2
min.:
0
value (enter!)
max.:
7
Def.:
4
Selection of the source for error resetting.
The errors can only be confirmed if the error is no longer present.
Certain errors can be confirmed only by turning the regulator off and back on;
see the error list.
Automatic reset via parameter 1.181.
0 = manual reset is not possible
1 = rising edge on digital input 1
2 = rising edge on digital input 2
3 = rising edge on digital input 3
4 = rising edge on digital input 4
5 = Foil keypad (confirm key)
6 = Analog input 1 (must be selected in parameter 4.030)
7 = Analog input 2 (must be selected in parameter 4.060)
1,181
Automatic reset function
Unit: s
Relation with
the parameter:
1,180
1,182
Parameter
manual:
P. xy
Acquisition
status:
2
min.:
0
value (enter!)
max.:
1000000
Def.:
0
In addition to the reset function (1.180), it is possible to select an automatic
reset of the errors.
0
= no automatic confirmation
> 0
= time for the automatic reset of the error
in seconds