Te chni cal dat a
User instructions. DGM speed regulator
151
8.1.2
General technical data for 230 V devices
Size
A
E
le
c
tri
c
da
ta
Recommended motor
power
1)
[kW]
0.37
0.55
0.75
1.1
Network voltage
1 x 100 VAC -15 %...230 VAC +10 %
140 VDC -15 %...320 VDC +10 %
Network frequency
50/60 Hz ± 6 %
Electric systems
TN / TT
Input current [A]
4.5
5.6
6.9
9.2
Actual nominal output
current [IN at 8 kHz]
2.3
3.2
3.9
5.2
Min. brake chopper
[Ω]
50
60 sec. overload in %
150
Switching frequency
4 kHz, 8 kHz, 16 kHz, (default 8 kHz)
Output frequency
0 Hz
– 400 Hz
Network start /
reconnecting cycles
Every 2 min.
Contact current
DIN EN 61800-5
< 10 mA
Fu
nc
ti
on
s
Protection functions
Overvoltage and undervoltage, I
2
t limitation, shortcircuit, ground fault, motor and inverter temperature,
tilting prevention, block detection, dry PID operation protection
Software functions
Process regulation (PID), fixed frequencies, dataset switching, quick restart, motor of current limitation
Soft PLC
IEC61131-3, FBD, ST, AWL
M
e
c
ha
n
ic
a
l
d
a
ta
Housing
Pressure die-cast aluminum housing in two parts
Dimensions
[L x W x H] mm
233 x 153 x 120
Weight, inc. adapter
plate
3.9 kg
Protection class [IPxy]
IP 65
Cooling
passive cooling
E
nv
iron
me
nt
a
l
c
on
d
it
ion
s
Room temperature
-10 °C (without condensation) up to +40 °C (50 °C with derating)
Storage temperature
-
25 °C…+85°C
Installation altitude
up to 1000 m s.l.m. / above 1000 m with reduced power (1% every 100 m) /
above 2000
m see the chapter “Power derating based on installation altitude”
Air relative humidity
≤ 96 % no condensation allowed
Vibration resistance
(DIN EN 60068-2-6)
50 m/s²; 5…200 Hz
2)
Shock resistance
(DIN EN 60068-2-27)
300 m/s²
EMC
(DIN-EN-61800-3)
C1
230 V device technical data (subject to technical changes)
1
Recommended motor power (4-pole asynchronous motor) with network voltage equal to 230 VAC.
2
Vibration test combined with degree of precision 2 according to FN942017, part 4.