12/16
Operating Instructions ACU
153
10 - Abs. value fixed frequency (FF)
Fixed frequency according to
Fixed Frequency Change-
Over 1
66
and
Fixed Frequency Change-Over 2
67
as
well as the current data set.
11 - Abs. value MFI1A + FF
Combination of operation modes 10 and 1.
12 - Abs. Value EM-S1INA + FF
1)
Combination of operation modes 10 and 2.
14 - Abs. Value MFI1A + EM-S1INA+FF
1)
Combination of operation modes 10, 1 and 2.
20 - Abs. value Motorpoti (MP)
Reference value source: Function
Frequency Motorpoti
Up
62
and
Frequency Motorpot. Down
63
21 - Abs. value MFI1A + MP
Combination of operation modes 20 and 1.
22 - Abs. Value EM-S1INA + MP
1)
Combination of operation modes 20 and 2.
24 -
Abs. Value MFI1A + EM-S1INA +
MP
1)
Combination of operation modes 20, 1 and 2.
30 - Abs.Val. Speed Sensor 1 (F1)
The frequency signals in
Operation Mode
490
are
evaluated as a reference value.
31 - Abs. value MFI1A + F1
Combination of operation modes 30 and 1.
32 - Abs. Val. Rep. Freq./PWM Inp. (F3)
The frequency signal on the digital input according to
Operation Mode
496
for the PWM/repetition frequency
input.
33 - Abs. value MFI1A + F3
Combination of operation modes 1 and 32.
34 - Abs.Val. Speed Sensor 2 (F2)
2)
The frequency signals of speed sensor 2 are evaluated
as a reference value.
35 - Abs. value MFI1A + F2
Combination of operation modes 1 and 35.
40 - Abs. value Motorpoti (KP)
KP 500 is the reference value source, with keys
▲
for
increasing the frequency and
▼
for reducing the
frequency.
41 - Abs. value MFI1A + KP
Combination of operation modes 40 and 1.
42 - Abs. Value EM-S1INA + KP
1)
Combination of operation modes 40 and 2.
44 - Abs. Value MFI1A + EM-S1INA +
KP
1)
Combination of operation modes 40, 1 and 2.
80 -
Abs. value MFI1A + FF + KP + F3 +
(EM-S1INA)
1)
Combination of operation modes 1, 10, 40, 32 and 2.
1)
81 - Abs. value MFI1A + FF + KP + F1 +
F3 + (EM-S1INA)
1)
Combination of operation modes 1, 10, 40, 30, 32 and
2.
1)
82 -
Abs. value MFI1A + FF + KP + F3
+ (F2)
2)
+ (EM-S1INA)
1)
Combination of op. modes 1, 10, 40, 32, 34
2)
and 2
1)
89 - Abs. value MFI1A + FF + KP + F1 +
F3 + (F2)
2)
+ (EM-S1INA)
1)
Combination of op. modes 1, 10, 40, 30, 32, 34
2)
and
2.
1)
90 -
Abs. value MFI1A + FF + MP + F3
+ (EM-S1INA)
1)
Combination of operation modes 1, 10, 20, 32 and 2.
1)
91 - Abs. value MFI1A + FF + MP + F1
+ F3 + (EM-S1INA)
1)
Combination of operation modes 1, 10, 20, 30, 32 and
2.
1)
92 -
Abs. value MFI1A + FF + MP + F3
+ (F2)
2)
+ (EM-S1INA)
1)
Combination of the operation modes 1, 10, 20, 32
(+ absolute amount speed sensor 2 (F2))
2)
(+ analog input extension module).
1)
99 -
Abs. value MFI1A + FF + MP + F1
+ F3 + (F2)
2)
+ (EM-S1INA)
1)
Combination of operation modes 1, 10, 20, 30, 33, 32
2)
and 2.
1)
101 to 199
Operation modes with signs (+/-).
1)
The reference value source is only available if an extension module with analog input is connected. For
information, refer to the extension module operating instructions.
2)
The reference value source is only available if an extension module with speed sensor input is connected.
For information, refer to the extension module operating instructions.