12/16
Operating Instructions ACU
67
7.5.3
Size 5 ACU 401 (18.5 to 30.0 kW)
DANGER
Disconnect the frequency inverter from mains voltage and protect it against being
energized unintentionally.
Verify safe isolation from power supply.
Work on the device may only be started once the DC link capacitors have discharged.
The time to wait is at least 3 minutes in the case of size 5.
When the frequency inverter is disconnected from power supply, the mains, DC-link
voltage and motor terminals may still be live for some time.
Switch off power supply
before connecting or disconnecting the mains cable to/from
terminal
X1,
the motor cables and the brake resistor to/from terminal
X2
.
Mains connection ACU 401 (18.5 to 30.0 kW)
0.5 … 35 mm
AWG 20 … 2
2
18.5 kW … 30.0 kW
PHOENIX MKDSP 25/ 6-15,00-F
0.5 … 25 mm
AWG 20 … 4
2
1.00 … 25 mm
AWG 18 … 4
2
1.5 … 25 mm
AWG 16 … 4
2
+
-
L1
L2 L3
L1
L2 L3
PE
3ph / 400V AC
X1
X1
2.5 Nm
22.1 lb-in