12/16
Operating Instructions ACU
145
Examples of reference positioning as a function of the parameter settings selected.
The reference point is registered according to parameter
Signal source
459
in operation mode 16–
S6IND, pos. edge by a signal on digital input 6.
The
Positioning distance
460
with parameter value 0.000U (default) defines a direct stop of the
drive with the deceleration behavior selected in parameter
Operation Mode
630
, and the set
Deceleration (Clockwise)
421
. If a
Positioning distance
460
is set, positioning is done at the set
deceleration.
The
Signal correction
461
of the signal run time from the measurement point to the frequency
inverter is not used if it is set to 0ms.
The
Load correction
462
can compensate a faulty positioning by the load behavior. By default, this
function is deactivated, i.e. set to 0.
The
Activity after positioning
463
is defined by operation mode 0–End positioning.
The
Time to wait
464
is not considered because operation mode 0 is selected for parameter
Activity
after positioning
463
.
The actual
value Rotations
470
enables a direct comparison with the required
Positioning distance
460
. In the case of deviations, a
Signal correction
461
or
Load correction
462
can be performed.
13.6.2
Axle Positioning
For axle positioning, a speed feedback system is required. In most cases, an additional extension
module is required for evaluation. The operation mode for parameter
Operation Mode Speed Sensor
2
493
is to be set to 1004 or 1104.
For information on how to set the parameter, refer to the
instructions on the optional extension module. The positioning is started if a start signal is received
and the frequency drops below an adjustable frequency limit. The machine stops with the selected
stopping behavior at the entered position angle.
To ensure the correct function of the axis positioning, the speed controller should be optimized after
the guided commissioning. This is described in chapter "Speed controller".
Via parameter
Reference orientation
469
, the angle between the reference point and the required
position is entered.
If this value is changed while the machine is at a standstill, the positioning operation is carried out
again at a frequency of 0.5 Hz. For this, a stopping behavior must be selected for the parameter
Operation Mode
630
which impresses a starting current either permanently when the drive is at a
standstill or for the stopping time (refer to chapter "13.2 "13.2").
Parameter
Setting
No.
Description
Min.
Max.
Factory setting
469 Reference orientation
0.0°
359.9°
0.0°
WARNING
During the positioning operation, the direction of rotation of the drive may change,
regardless of whether the command Start clockwise or Start anticlockwise was
activated.
Make sure that the change of the direction of rotation cannot result in any personal or
material damage.
The
positioning
is
started
by
a
start
command
from
a
signal
source
(e. g. digital input), which must be assigned to parameter
Start Positioning of Axle
37
. The signal
source can be selected from the operation modes for digital inputs described in chapter "".
The positioning starts on condition that the
Actual Frequency
241
of the output signal is smaller
than the value entered in parameter
Positioning Frequency
471
. Due to a stopping behavior, the
actual frequency drops below the positioning frequency.