104
Operating Instructions ACU
12/16
The rated data of the motor are to be entered according to the specifications on the
rating plate for the motor connection type used (star or delta connection).
If the data
entered deviate from the rating plate, the parameters will not be identified correctly.
Parameterize the rated data according to the rating plate of the motor for the wiring
of the motor winding. Consider the increased rated current of the connected three-
phase motor.
Example
: BONFIGLIOLI BN 90LA Motor
Parameter
Star
Delta
370 Rated Voltage
400 V
230 V
371 Rated Current
3.7 A
6.4 A
372 Rated Speed
1410 min
-1
1410 min
-1
374 Rated Cosinus Phi
0.77
0.77
375 Rated Frequency
50 Hz
50 Hz
376 Rated Mech. Power
1.5 kW
1.5 kW
9.2.5
Plausibility check
After the machine data (and the speed sensor data, if applicable) have been
entered, the calculation or examination of the parameters is started automatically.
The display changes over to "CALC" for a short time. If the verification of the
machine data is successful, the guided commissioning procedure continues with the
identification of the parameters.
Verification of the machine data should only be skipped by experienced users. The
configurations contain complex control processes which depend to a large degree on
the correctness of the machine parameters entered.
The warning and error messages displayed during the verification process have to be
observed. If a critical condition is detected during the guided commissioning, it is
displayed by the control unit. Depending on the deviation from the expected
parameter value, either a warning or an error message is displayed.
To ignore the warning or error messages, press the ENT key. The guided
commissioning is continued. However, it is recommended that the data be checked
and corrected if necessary.
To correct the entered parameter values after the warning or error message, press
the ESC key. Use the arrow keys to switch to the parameter value which is to be
corrected.
If an error message is displayed, the rated values must be checked and corrected.
The guided commissioning procedure is the rated values have been entered
correctly. Aborting the guided commissioning procedure by pressing ESC key should
only be done be expert users because it may be possible that rated values have not
been entered or determined correctly.