Operating Instructions ACU
245
19.7
Functions of field-oriented control
The field-oriented control systems are based on a cascade control and the calculation of a complex
machine model. The various control functions can be supplemented by special functions specific to
the application.
19.7.1
Motor chopper
The field-oriented control systems contain the function for adapted implementation of the generator
energy into heat in the connected three-phase machine. This enables the realization of dynamic
speed changes at minimum system costs. The torque and speed behavior of the drive system is not
influenced by the parameterized braking behavior. The parameter
Trigger Threshold
507
of the DC
link voltage defines the switch-on threshold of the motor chopper function.
Parameter
Setting
No.
Description
ACU
Min.
Max.
Factory setting
507 Trigger Threshold
201
225.0 V
1000.0 V
400.0 V
401
425.0 V
800.0 V
501
925.0 V
1050.0 V
800.0 V
601
1225.0 V
1400.0 V
1150.0 V
The parameter
Trigger Threshold
507
is to be set in such a way that it is between the maximum DC
link voltage which the mains can generate and the maximum admissible DC link voltage of the
frequency inverter.
max
dMC
Netz
Ud
U
2
1,1
U
If the parameter
Trigger Threshold
507
is set larger than the maximum admissible DC link voltage,
the motor chopper cannot become active, the motor chopper is switched off.
If the set
Trigger Threshold
507
is smaller than the maximum DC link voltage the mains can
generate, error message F0706 (see Chapter 21.1.1 "21.1.1") is displayed when the frequency
inverter is switched on.
The motor chopper function will only work if it was activated via the voltage controllers
Operation Mode
670
. See Chapter 18.2 "18.2".
For synchronous motors (
Configuration
30
=5xx or 6xx), the motor chopper feature is
deactivated to prevent the motor from being damaged. The other functions of the
voltage controller are not affected by this.
Note that, by default, the motor chopper
Trigger Threshold
507
and brake chopper
Trigger Threshold
506
are set to different values. When using both functions make
sure the set thresholds are suitable for the application.