12/16
Operating Instructions ACU
107
SA031 Shorten Motor Line using Switchfrequ. 16 kHz.
SA032 Shorten Motor Line using Switchfrequ. 12 kHz and higher.
SA033 Shorten Motor Line using Switchfrequ. 8 kHz and higher.
SA041 The slip speed was not determined correctly. Check the values for parameters Rated Speed
372
and Rated Frequency
375
.
SA042 The slip speed was not determined correctly. Check the values for parameters Rated Speed
372
and Rated Frequency
375
.
SA051 The machine data for star connection were entered, the motor, however, is connected in
delta. For star operation, change the motor cable connection. For delta operation, check
the entered rated motor values.
Repeat the parameter identification
SA052 The machine data for delta connection were entered, the motor, however, is connected in
star. For delta operation, change the motor cable connection. For star operation, check the
entered rated motor values.
Repeat the parameter identification
SA053 A phase asymmetry was measured. Check the cables at the terminals of the motor and the
frequency inverter for proper connection and check the contacts for corrosion.
SA054 Resolver offset not adjusted.