Table 10-31. S2000R-Siren Mode Indication
Mode
LED Performance
Start
Illuminates with green for 1 s
Battery depassivation:
−
Depassivation in progress or periodic testing of
the battery
Flashes with amber 15 times per four
seconds
Table 10-32. Link Quality Indication
LED Performance
Condition
Flashes with green
Strong signal
Flashes with green and red
Normal signal
Flashes with red
Weak signal (not recommended to install)
Shows solid red light for 1 s
No communications or the device is not connected to
the ARR32
Getting Started
Connect the supplied batteries to the BAT1 and BAT2 terminals observing polarity (sequence of
connection makes no difference).
Just after connecting the batteries the alarm inspects their conditions. If even one of the two
connected batteries is operable the alarm starts operation with the relevant indication.
Being in quiescent mode the alarm tests the batteries every 12 hours.
After the S2000R-Siren is connected to the ARR32, the procedure of depassivation is started.
The depassivation procedure activates batteries after long term storage and can take up to 5 minutes.
The process of depassivation is indicated as shown in Table 10-31. If depassivation fails the device
indicates low battery condition.
Connecting and Programming
Connect the alarm to the ARR32 and set its parameters in the configuration of the polling loop
controller as discussed in Sections 6, 7, and 8 of this Manual.
The S2000R-Siren occupies two successive addresses within the polling loop:
A first address for light alarms, and
A second address for sound alarms.
Due to powering by standalone power supplies of limited capacity it is strongly
recommended to assign Sirena tactics for both output while programming the S2000R-
Siren in the configurations of the polling loop controller and the S2000 control panel