Addressable Radio Link System
www.bolid.ru
32
To set the required interval, select the ARR32 in Device Area and select the relevant value in the
drop-down list Poll Interval on the Properties tab in Data and Control Area. Restart the ARR32 in
order the changes to be saved and come into force.
ACCESS CONTROL
Access to controlling and programming the ARR32 by means of Configurator can be password
protected. A password is stored in the memory of the ARR32 and is requested in case of an attempt
to connect the ARR32. In Device Search window an ARR32 protected by password appears with a
key icon
at the left side of the string.
Figure 7-10
On an attempt to connect to an ARR32 protected by a password the Password Required window
appears. Until the correct password is entered Configurator doesn’t provide any information about the
connected ARR32 and doesn’t provide access to the control functions of Configurator.
Figure 7-11
All the ARR32 operating on the same radio channel should poll the detectors with the
same Poll Interval. If the Auto Mode with Dynamic Channel Selection is used to select a
channel then the poll interval for the radio link detectors should be identical for all the
ARR32 in the radio coverage range.
WARNING: The time of system response doesn’t depend on Device Poll Interval.
Please do not set Device Poll Interval to a value less than 30 s unless necessary
The defined Poll Interval is not applied to output devices such as relays and light and
sound alarms.
Output devices are always polled with a constant, unchangeable period (see manuals for
the relevant devices)