S2000R
S2000R-IPR
55
www.bolid.ru
S2000R-IPR
General
S2000R-IPR Radio Link Resettable Manual Call Point (hereinafter
referred to as the call point) is to be used in fire alarm and fire
suppression systems to trigger a fire alarm or to activate the fire
suppression system manually.
The case of the call point has a protective flip cover which can be
sealed.
The call point is switched to Fire conditions by pressing on the
central plastic operation element, the central element then being
mechanically latched.
The call point can be simply returned from the Fire Alarm state to the
Normal state with a special key provided.
The call point monitors its tamper condition, battery status, and radio link quality.
The call point is intended for round-the-clock operation.
The elements of the call point are the following:
1: The hole to insert the key to reset the activated call point;
2: The holes to insert the key to open the call point case;
3: The special key (provided) to reset the activated call point and to open its case;
4: The place to apply a seal.
Specifications
Table 10-9. S2000R-IPR Specifications
Batteries:
Main
Backup
ER14505 (
АА
), 3.6 V
CR2032, 3 V
Operating on Battery in Quiescent Mode*:
By the main battery
By the backup battery
6-12 years
2 months min
Ingress Protection Rating
IP41
Operating Temperature
-30 to +50°
С
Transportation and Storage Temperature
-30 to +55°
С
Weight
0.140 kg
Overall Dimensions
94 mm
х
90 mm
х
33 mm
* - Operation time depends on the transmission interval, radio link quality, and ambient temperature