Addressable Radio Link System
www.bolid.ru
36
Type of the Device
Type of the Input
S2000R-IK Rev.02
5: Intrusion with Tamper Monitoring
7: Entrance
S2000R-SHIK
5: Intrusion with Tamper Monitoring
7: Entrance
S2000R-ASR2
Pulse Input 1
13: Counting
Pulse Input 2
13: Counting
Flood Detector
17: Flood
S2000R-ASR1
13: Counting
OUTPUTS
Control modules S2000R-Siren, S2000R-OST, S2000R-RM, and S2000R-RM rev.01 should be
assigned with one of the Control Programs by means of UProg (see the User’s Manual for the polling
loop controller).
You should select a Control Program so that the relevant device can operate as required by your
installation.
DEVICE INDICATION CONTROL
The devices of the S2000R Series do not support controlling their light indication by the polling loop
controller. So, only the following values can be selected for the Device Indication Control parameters
of the addressable devices in UProg:
0: Indication Disabled;
1: Standalone Indication Control.
SETTING ADDRESSES
While assigning polling loop addresses in the configuration of the polling loop controller, in order a
programmed S20000R device to capture a given address send a Program Loop Address command to
the device and briefly press the Prog button on the device PCB (refer to the User’s Manual of the
relevant device).
For S2000R-IP and S2000R-DIP detectors this also can be done by pressing the relevant detector
light emitter down or lighting the light emitter by the laser beam of a laser test tool.
For an S2000R-ASR1 pulse adapter set a magnet to the service contact for a short time.