S2000R
37
www.bolid.ru
DEFEAT PROTECTION FOR S2000R-SMK
Defeat protection of an S2000R-SMK magnetic contact (see the relevant section of this Manual) is
enabled by setting on the active state for the Defeat Protection field in UProg (the active state is
indicated by a plus sign «+»). This setting should be done only for the base address of the S2000R-
SMK.
POWER SAVING MODE FOR S2000R-IK, S2000R-IK REV.02, AND S2000R-SHIK
The function of power saving mode for S2000R-IK, S2000R-IK rev.02, and S2000R-SHIK detectors
(see the relevant sections of this Manual) is turned on by selecting the active state for the Save Mode
field in UProg (the active state is indicated by a plus sign «+»).
Arming the detectors operating in the power saving mode can take a time within Device Poll Interval
(see Section Setting Device Poll Interval). In order the system to operate correctly the arming delay
for the detectors should be defined no less than Device Poll Interval.
COUNTING THRESHOLD FOR S2000R-ASR2 AND S2000R-ASR1
ARR32 transmits the polling loop controller readings of counting inputs when these reading values
exceed a given Counting Threshold (upon accumulation the given difference of readings).
This threshold value is set in UProg in the field Counting Threshold.