S2000R
S2000R-DIP
49
www.bolid.ru
S2000R-DIP
General
S2000R-DIP Radio Link Analog Addressable Photoelectric Smoke
Detector (hereinafter referred to as the detector) is designed to protect
premises against fire by monitoring the smoke level values in its
smoke chamber and sending alarms when the smoke level exceeds
the preset values. The detector provides monitoring of current smoke
and dust levels in its smoke chamber. The detector also monitors its
case against tampering and separation from the attachment point as well as keeps a check on main
and backup battery voltage and quality of the radio link.
The detector is intended for round-the-clock operation.
The detector’s operability can be tested with the help of a laser test tool such as made by System
Sensor or similar.
Specifications
Table 10-5. S2000R-DIP Specifications
Batteries:
Main
Backup
ER14505 (
АА
), 3.6 V
CR2032, 3 V
Operating on Battery in Quiescent Mode*:
By the main battery
By the backup battery
4-8 years
2 months min
Sensitivity
0.05 - 0.2 dB/m
Response Time
10 s max
Fault Detection Time
60 s max
Ingress Protection Rating
IP40
Operation Temperatures
-25 to +55°
С
Transportation and Storage Temperature
-30 to +55°
С
Weight
0.12 kg
Overall Dimensions, Diameter
×
Height
100 mm
×
48 mm
* - Operation time depends on the transmission interval, radio link quality, and ambient temperature