Use of the control
5.2
Compressed airnet view
Page 50
BOGE compressor control airtelligence provis 3
Event display
The event display shows all important events or messages that are available
for the compressed airnet. In addition to information about which events
occurred when, the event display also offers the possibility to edit the events /
messages, i.e. to confirm or acknowledge them.
Fig. 5.11: Compressed airnet view - event display
There are four types of events:
Tab. 5.4: Event types
The events are listed in the list area (1) according to their chronological order.
In case of the Fig. 5.11: there is an event at the top, it is a warning because it
is indicated in the "Status" column with an orange triangle. Further information
No.
Symbol
Event
Meaning
1
Internal system message
Concerns the airtelligence provis 3
control itself.
2
Information message
Important information (about the com-
pressed airnet) is available.
3
Warning/Servicing mes-
sage
There is a warning or servicing mes-
sage on the control or in the com-
pressed airnet, or on a component of
the compressed airnet. All compo-
nents are still operational and the com-
pressed air supply is guaranteed.
4
Fault
There is a fault in the control or in the
compressed airnet, or in a component
of the compressed airnet.
The compressed air supply is at risk. In
the event of critical faults that no lon-
ger guarantee the function of the con-
trol system or the compressed airnet,
the compressors are released (analo-
gous to the operating mode „All re-
leased“). If a component is faulty, the
component is switched off.
(1)
(3)
(2)