MKF+ MKFT (E3.2) 07/2017
page 49/115
9.4
Selecting between set-point ramp and set-point step
Set-points always refer to the start of a program section, i.e., at the beginning of each program section
the entered set-point is targeted. During program section operation, the temperature or humidity gradually
passes to the set-point entered for the next program section.
By appropriate planning of the program section timing, you can enter all kinds of temperature and humidi-
ty transitions.
•
Gradual temperature / humidity changes “set-point ramp”
The set-point changes its value gradually while proceeding from one program section to the next one
during the programmed section length. The actual temperature or humidity value (X) follows the con-
tinually moving set-point (W) at any time.
•
Program sections with constant temperature / humidity
The initial values of two subsequent program sections are identical; so the temperature or humidity
remains constant during the whole time of the first program section.
•
Sudden temperature / humidity changes “set-point step”
Steps are temperature or humidity changes (ramps) that occur during a very short interval. A section
with a different set-point follows two program sections with an identical set-point. If the duration of this
transitional program section is very short (minimum entry 1 sec), the temperature or humidity change
will proceed rapidly within the minimum amount of time.
Figure 17: Possible temperature or humidity transitions
The following chapter offers examples of programming a set-point ramp and a set-point step.
9.5
Program entry as set-point ramp or as set-point step
In order to avoid incorrect programming, we recommend plotting both the temperature and humidity pro-
files (chart templates in chap. 9.11 and 9.12) and entering the values into a table (templates in chap. 9.13
and 9.14).
The controller provides 8 operation lines that can be activated or de-activated for each program section.
Operating contact 1 can be used to control the bedew protection (chap. 10). Operation lines 2 to 5 serve
to switch any device connected to the zero-voltage relay outputs (DIN sockets (11) and (12), chap. 11).
Operation line 8 releases the compressed air dryer (option, chap. 16.7). The other operation lines are
non-functional.
01
02
03
04
05
06
07
08
09
W
t
Содержание MKF 115
Страница 97: ...MKF MKFT E3 2 07 2017 page 97 115 20 10 Dimensions MKF 115 MKFT 115...
Страница 98: ...MKF MKFT E3 2 07 2017 page 98 115 20 11 Dimensions MKF 240...
Страница 99: ...MKF MKFT E3 2 07 2017 page 99 115 20 12 Dimensions MKFT 240...
Страница 100: ...MKF MKFT E3 2 07 2017 page 100 115 20 13 Dimensions MKF 720 MKFT 720...
Страница 102: ...MKF MKFT E3 2 07 2017 page 102 115...
Страница 103: ...MKF MKFT E3 2 07 2017 page 103 115...
Страница 104: ...MKF MKFT E3 2 07 2017 page 104 115 21 2 EU Declaration of Conformity for MKFT...
Страница 105: ...MKF MKFT E3 2 07 2017 page 105 115...
Страница 106: ...MKF MKFT E3 2 07 2017 page 106 115...
Страница 108: ...MKF MKFT E3 2 07 2017 page 108 115...
Страница 109: ...MKF MKFT E3 2 07 2017 page 109 115 22 Product registration...