U
SER
’
S
AND
I
NSTALLER
’
S
M
ANUAL
S
ETTINGS
Version: 4.0 (23-08-2007)
41
Multiple units operated from one single control panel
The output has always a
global
effect: the signals are always the
same in all units connected to the control panel.
4.5.6 Options and working of the unit output
O
PTIONS
F
UNCTION
NO
. 61
M
EANING
OF
THE
OUTPUT
SIGNAL
VALUE
WORKING
OUTPUT
1
OUTPUT
2
1 (default value)
normally
open
fault
maximum filter life lapsed
2
equal to value 1
3
normally
open
fault
heating deficit
4
normally
open
fault or maximum filter life
lapsed
heating deficit
5
normally
open
fault
no function
6
normally
open
fault or maximum filter life
lapsed
no function
7
normally
open
no function
heating deficit
8
normally
open
fault
air curtain is switched on
9
normally
open
fault or maximum filter life
lapsed
air curtain is switched on
13
To be used if you want the unit
to switch the central heating
system On/Off upon heating
being switched On/Off.
normally
open
no function
signal to central heating
system:
air curtain is switched On,
with heating
15
To be used if you want the
central heating system to be
switched On in case of risk of
freezing: see section
2.5.2
.
normally
open
fault
signal to central heating
system:
risk of freezing
51
normally
closed
fault
maximum filter life lapsed
•
Normally open
: The signal is activated when the contact is closed.
•
Normally closed
: The signal is activated when the contact is broken.