Version: 4.0 (23-08-2007)
37
4.4
Room temperature control
Working
The room temperature control allows you to prevent the air
curtain from overheating the room.
If the temperature in the room exceeds a certain value (the
set
point
), the discharge air temperature will be reduced to the
half temperature
.
You set the set point using function no. 5 at the manager’s
level (see section
4.2.3
).
The half temperature is the average of the set point and the
discharge air temperature, as pre-set by the user (see section
3.2 ’Selecting the air curtain strength’
).
Options
Function no. 51 at the installer’s level (see section
4.3.3
) allows
you to let the room temperature control work based on
either the temperature of the air taken in or the ambient tem-
perature near the control panel.
74
Discharge air temperature reading in
the display
0 = display pre-set discharge air
temperature
1 = display actual discharge air temperature
(default value).
The
- symbol appears in the display if
the discharge air temperature differs
from the pre-set temperature.
76
Release delay of external-control
input
See section
4.5.2
.
Pre-settable between 0 and 99 minutes
(default value = 0 (no delay)
91
92
93
94
95
Reading last 5 fault messages
91 = oldest message
95 = latest message
See also section
6.3.1
.
A = fault code
B = time lapsed
since
occurrence
(01 23 =
123 hrs)
A and B are displayed alternately.
X
98
Resetting control panel
Equal to function 71
X
N
O
.
F
UNCTION
O
PTIONS
Y
OUR
SETTING
A
B
room temperature
discharge air temperature