4.2.3 Functions at the manager’s level
N
O
.
F
UNCTION
O
PTIONS
Y
OUR
SETTING
1
Automatic temperature control or
fixed temperature for the air curtain
See also section
3.2
.
AU = automatic temperature control
(default value)
30, 35 or 40 °C = fixed temperature
HI = maximum discharge air temperature
With hot-water heating, the maximum
is 55 °C, with electric heating 50 °C.
2
Reading or resetting service life of
filter
Use this function when replacing or
cleaning the filter, see section
5.1
.
The service life is expressed in weeks.
Resetting after replacing or cleaning:
• press
and
simultaneously
You return to the user’s level immediately.
X
3
Maximum filter life
(service life, on expiry of which filter
is considered dirty)
See also section
5.1
.
Pre-settable between 1 and 52 weeks.
(default value = 26 weeks)
4
Enable/disable filter service life
tracking and displaying
See also section
3.4.1
.
0 = disable tracking and displaying
1 = enable tracking and displaying (default
value)
5
Room temperature control set point
See also section
4.4
.
Pre-settable between 15 and 30 °C
(default value = 25 ºC)
9
Adjusting control panel temperature
reading
Use this function if the displayed room
temperature differs from the actual
temperature due to unfavourable
position of the control panel.
Pre-settable between -3 and +3 °C
(default value = 0 ºC (no adjustment))
10
Reading or deleting current faults
See also section
6.3
.
Browsing and reading list:
• press
or
Deleting faults:
• press
and
simultaneously
You return to the user’s level immediately.
X
11
Default settings at the manager’s level
dF = all functions have default values
-- = there are functions with deviating
values
To default all values:
• press
and
simultaneously
• press
for 3 seconds
Function nos. 2 and 10 are not affected.
X