- 32 -
D.H.W. fLoW SWITCH, fILTER AND fLoW LIMITER
14.6 flow limiter
The M110B.24SM/... model is factory fitted with a 10 litre/min.
flow limiter.
If on the M110B.32SM/... model the flow rate of the d.h.w. circuit
is too high, it is possible to limit it by installing a flow limiter. The
following sizes are available:
Nominal flow rate (litres/min)
Colour
10
Blue
12
Red
14
Pink
To install the flow limiter:
1 Remove the flow switch group as explained in the section
"Removal of the flow switch group and d.h.w. circuit filter"
page 31.
2 Separate the flow switch plug 1 from the body 4 (Figure 14.4)
levering with a screwdriver one of the two hooks.
figure 14.4
4
1
3 Insert the flow limiter 3 as shown in Figure 14.3.
4 Reassemble the group following the above sequence in re-
verse order.