30
DEFAULT PARAMETER SETTINGS TABLE
CHECKS
Menu
Description
Setting range
Default
ACS 160
Default
ACS 225
5. SETTINGS
5.1
T setpoint
30°C ÷ 47°C
45°C
45°C
5.2
T max
50°C ÷ 99°C
52°C
52°C
5.3
Primary flow min.
40°C ÷ 59°C
50°C
50°C
5.4
Primary flow max.
49°C ÷ 99°C
60°C
60°C
5.5
Cold water
0°C ÷ 60°C
10°C
10°C
5.6
VFS type
10 - 200 l/min
10 - 200 l/min
5.7
Comfort
On / Off
Off
Off
5.8
Circulation
Off / Request / Periods
Request
Request
5.9
Purging time
1 ÷ 180 min
2 min.
2 min.
5.10
Circulation pause time
1 ÷ 20 min
20
20
5.11
Circ. Tmin
10°C ÷ 90°C
35°C
35°C
5.12
Circulation hysteresis
1K ÷ 20K
5K
5K
5.13
Circ. max. FR
1 l/min ÷ 100 l/min
15
15
5.14
Circulation period
-
-
6. SPECIAL FUNCTIONS
6.1
Time and date
-
-
-
6.2
Sensor calibration
-
-
-
6.2.1
S1 calibration
−100 ÷ 100
0
0
6.2.2
S2 calibration
−100 ÷ 100
0
0
6.2.3
S3 calibration
−100 ÷ 100
0
0
6.2.4
S4 calibration
−100 ÷ 100
0
0
6.2.5
S5 calibration
−100 ÷ 100
0
0
6.2.6
S6 calibration
−100 ÷ 100
0
0
6.3
Setup wizard
-
-
-
6.4
Factory settings
-
-
-
6.5
Mixer
-
-
-
6.5.1
Turn time
0,1 sec ÷ 3 sec
0,5 sec
0,5 sec
6.5.2
Pause factor
0,1 ÷ 4
1,5
1,5
6.5.3
Increase
0 ÷ 20
0
0
6.6
Anti-legionella
-
-
-
6.6.1
AL function
On / Off
Off
Off
6.7
Speed control
-
-
-
6.7.1
Max. speed
70% ÷ 100%
100%
100%
6.7.2
Min. speed
12% ÷ 95%
25%
25%
6.7.3
Pump μ0
0 ÷ 1,5 V
0,7 V
0,7 V
6.8
Auxiliary pump
-
-
-
6.8.1
Flow on
20 l/h ÷ 200 l/h
50 l/h
70 l/h
6.8.2
Flow off
10 l/h ÷ 40 l/h
30 l/h
40 l/h
6.8.3
Delay
1 sec ÷ 60 sec
3 sec
3 sec
6.9
Limescale protection
On / Off
On
On
6.9.1
Limescale protection
5 sec ÷ 60 sec
20 sec
20 sec
On completion of the installation, perform the checks listed in the table below.
DESCRIPTION
OK
All automatic or manual filling pumps removed.
Safety valve calibrated to 6 bar, and flow open.
Drain pipe from safety valve routed suitably.
Expansion vessel correctly located and pre-charged to 2.5 bar
Non-return valves activated as gravity brakes