REPLACING THE CONTROLLER FUSE
REPLACING THE CONTROL PANEL FUSE
b
Repairs and maintenance must be entrusted exclu-
sively to an expert service technician. Make sure
that power has been disconnected from the control-
ler before commencing any work on it.
b
Use only the spare fuse supplied, or select a similar
fuse with the following specifications: T2A 250V
If the controller is connected to the power supply and does
not come into operation, or the display remains blank, the
internal fuse could be defective. In this situation, open up
the controller, remove the fuse and inspect it.
Replace the fuse with a new one of identical characte-
ristics. Ascertain the cause of the fault (e.g. pump) and
replace it. Once the controller is powered up, make the
settings and check the operation of the outputs in manual
mode (function 4.2).
b
Repairs and maintenance must be entrusted exclu-
sively to an expert service technician. Make sure
that power has been disconnected from the control
panel before commencing any work on it.
b
Use only the spare fuses supplied, or select similar
fuses with the following specifications: Dim. 10.3x38
10A gG.
N.B.:
There are two fuses, one in each fuse holder.
Loosen the screws at each corner of the control panel
cover and remove the cover.
Pull down the black levers to open the fuse holders and
pull out the fuses.
Replace the blown fuse with another of the same type.
Close the fuse holders and replace the cover of the con-
trol panel, taking care not to pinch any wires.
Fuse