FONTE 11-14 AP
15
PROBLEM
CAUSE
SOLUTIONS
There is no spark
- electrical cable of device is disconnected
- insert
- piezoelectric mechanism broken
- test, substitute
- piezoelectric mechanism is not earthed
- test
- the electrode is damaged
- substitute
the pilot does not switch on when
there is a spark
- pilot nozzle obstructed
- clean by blowing
- electrode activation position
- regulate
- no gas supply
- open the gas tap
- air in the gas tubes
- release gas
the pilot does not stay on
- thermocouple consumed
- substitute
- broken magnet
- substitute
pilot on but the main burner does not
ignite
- insufficient water pressure
- repair the device pressure
- rotate the knob completely to the right
- the membrane is broken
- substitute
the burner does not switch off when
the water turns off
- grime on the gas shutter
- test, clean
- valve piston or stem is locked in open posi
-
tion
- disassemble, clean and eventually substitute
- If an LPG supply, check the gas pressure
- regulate and if necessary substitute the tank
pressure regulator
delayed burner activation
- pilot burner flame is too far from main burner
flame or is too short
- regulate the flame, clean injector and pilot bur
-
ner
the exchanger blade becomes dirty
in a small amount of time
- poor draught or dusty surroundings
- check the smoke channel efficiency
- yellow flame
- Check the gas type and clean the burner
- excess gas consumption
- check and regulate
there is a smell of gas
- due to the loss of gas in the tubes, check the
tubes and find the leak
- do not activate electric switches or any object
that produces sparks in local area
there is a smell of gas
- it can be caused by obstruction in the flue gas
circuit
- check the efficiency of the smoke channel
and the flue gas conduit
- excess gas consumption
- check and regulate