EN
Installation and operating manual
DRYPOINT
®
AC 410 – 495 | DRYPOINT
®
AC 410 – 495 MS
15
2.2. Type plate
The type plate is attached to the container of the DRYPOINT
®
AC.
Manufacturer:
BEKO TECHNOLOGIES GmbH
Im Taubental 7
D-41468 Neuss
Art-Nr.
Item number
N° d´article
Anlage
Plant
Installation
Betriebsdruck
Operating pressure
Pression de fonctionnement
Serien-Nr.
Serial-no.
N° de serie
Baujahr
Year of manufacture
Anne de fabrication
Spannung / Leistungsaufnahme
Voltage / Power consumption
Voltage / Consommation électrique
Betriebstemperatur
Operating temperature
Temperature de service
Vorfilterelement
Prefilter element
Element du filter amont
Umgebungstemperatur
Ambient temperatur
Temperature ambiente
Nachfilterelement
Afterfilter element
Element du filtre à poussieres
Schutzklasse / Schutzart
Protection class / Type of protection
Classe de protection / Type de protection
xxxxxxxxxx
xxxxxxxxxxx
xx / 20xx
230 V - 50-60 Hz / 40 W
min. 5 °C / max. 50 °C
min. 4 °C / max. 50 °C
xxx
DP AC xxxx
1.
xxx
2.
N/A
3.
N/A
I / IP54
min. 4 bar / max. 16 bar
NOTE
Handling of type plate
Do not remove or cover the type plate, and protect it against damage.
2.3. Product overview and description
2.3.1. Operating principle of adsorption dryer
2.3.1.1.
Prefilter with condensate drain
The medium to be dried is pre-filtered by a high-performance submicro filter. Oil, water and dirt particles are held
back by the micro-fibre fleece to a rate of 99.99998% for dirt particles larger than 0.01 µm.
The micro-fibre fleece is encased in a coalescing filter jacket and the medium flows from the inside outwards. In the
coalescing filter, the liquid aerosols and mists form larger droplets, which then drop into the bottom part of the filter
housing from where they are removed through the condensate drain from the system.
After the prefiltration stage, the residual oil content is smaller than 0.01 mg/m
3
(at a max. infeed concentration of
3 mg/m
3
).
2.3.1.2.
Afterfilter
The downstream dust filter removes fine dust with a particle size of < 25 µm from the compressed air.