Commissioning
EL1502, EL1512
66
Version: 3.5
Activation of the configuration
The allocation of PDO to PLC variables has now established the connection from the controller to the inputs
and outputs of the terminals. The configuration can now be activated with
or via the menu under
"TwinCAT" in order to transfer settings of the development environment to the runtime system. Confirm the
messages "Old configurations are overwritten!" and "Restart TwinCAT system in Run mode" with "OK". The
corresponding assignments can be seen in the project folder explorer:
A few seconds later the corresponding status of the Run mode is displayed in the form of a rotating symbol
at the bottom right of the VS shell development environment. The PLC system can then be started as
described below.
Starting the controller
Select the menu option "PLC" → "Login" or click on
to link the PLC with the real-time system and load
the control program for execution. This results in the message
"No program on the controller! Should the
new program be loaded?"
, which should be acknowledged with "Yes". The runtime environment is ready for
program start by click on symbol
, the "F5" key or via "PLC" in the menu selecting “Start”. The started
programming environment shows the runtime values of individual variables:
Fig. 69: TwinCAT development environment (VS shell): logged-in, after program startup
The two operator control elements for stopping
and logout
result in the required action
(accordingly also for stop "Shift + F5", or both actions can be selected via the PLC menu).
Содержание EL1502
Страница 1: ...Documentation EL1502 EL1512 Up down Counter 24 VDC 3 5 2018 06 08 Version Date ...
Страница 2: ......
Страница 71: ...Commissioning EL1502 EL1512 71 Version 3 5 Fig 76 Incorrect driver settings for the Ethernet port ...
Страница 126: ...Commissioning EL1502 EL1512 126 Version 3 5 Fig 151 EL1512 0000 0020 Standard scope of process data ...