Commissioning
EL1502, EL1512
149
Version: 3.5
Index 1C33 SM input parameter
Index (hex) Name
Meaning
Data type
Flags
Default
1C33:0
SM input parameter
Synchronization parameters for the inputs
UINT8
RO
0x07 (7
dec
)
1C33:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchronous with SM 3 event (no outputs
available)
UINT16
RO
0x0022 (34
dec
)
1C33:02
Cycle time
as
0x1C32:02 [
}
148]
UINT32
RO
0x00000000
(0
dec
)
1C33:03
Shift time
Time between SYNC0 event and reading of the inputs
(in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:04
Sync modes supported Supported synchronization modes:
• Bit 0: free run is supported
• Bit 1: synchronous with SM 2 event is
supported (outputs available)
• Bit 1: synchronous with SM 3 event is
supported (no outputs available)
UINT16
RO
0x8007
(32775
dec
)
1C33:05
Minimum cycle time
as
0x1C32:05 [
}
148]
UINT32
RO
0x00000000
(0
dec
)
1C33:06
Calc and copy time
Time between reading of the inputs and availability of
the inputs for the master (in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:08
Command
as
0x1C32:08 [
}
148]
UINT16
RO
0x0000 (0
dec
)
1C33:09
Delay time
Time between SYNC1 event and reading of the inputs
(in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:0B
SM event missed
counter
as
0x1C32:11 [
}
148]
UINT16
RO
0x0000 (0
dec
)
1C33:0C
Cycle exceeded
counter
as
0x1C32:12 [
}
148]
UINT16
RO
0x0000 (0
dec
)
1C33:0D
Shift too short counter as
0x1C32:13 [
}
148]
UINT16
RO
0x0000 (0
dec
)
1C33:20
Sync error
as
0x1C32:32 [
}
148]
BOOLEAN
RO
0x00 (0
dec
)