Commissioning
EL1502, EL1512
110
Version: 3.5
Fig. 137: "Process Data" tab
• Parameterization takes place via the
CoE objects [
}
130]
, indices 0x80xx (CoE - Online tab) (fig.
"CoE -
Online" tab
).
• Click on the row of the indexes to be parameterized and enter a corresponding value in the "
SetValue
"
dialog.
• After parameterization read in the configuration again. To do this, click on the button "
Reload I/O
devices
".
Fig. 138: "CoE – Online" tab
From the controller (TwinCAT PLC) the counter value can be set (index
0x7000:03 [
}
132]
,
0x7010:03 [
}
132]
,
0x7020:03 [
}
133]
), the counter function of the terminal inhibited (index
0x7000:04 [
}
132]
,
0x7010:04 [
}
132]
,
0x7020:04 [
}
133]
) and the outputs activated (index
0x7000:02 [
}
132]
,
0x7010:02 [
}
132]
,
0x7020:02 [
}
133]
,
EL1502 only). In addition an internal function can be activated that enables the automatic setting of outputs
with defined counter values (index
0x8000:01 [
}
130]
,
0x8010:01 [
}
130]
,
0x8020:01 [
}
131]
, EL1502 only).
Содержание EL1502
Страница 1: ...Documentation EL1502 EL1512 Up down Counter 24 VDC 3 5 2018 06 08 Version Date ...
Страница 2: ......
Страница 71: ...Commissioning EL1502 EL1512 71 Version 3 5 Fig 76 Incorrect driver settings for the Ethernet port ...
Страница 126: ...Commissioning EL1502 EL1512 126 Version 3 5 Fig 151 EL1512 0000 0020 Standard scope of process data ...